NEWS

CISA Warns of Critical Unpatched Danfoss AK-SM 8xxA Flaw (CVE-2026-129713) in Refrigeration Controllers

A stack buffer overflow (CVSS 9.8) in Danfoss AK-SM 8xxA controllers can allow unauthenticated code execution. Fix is planned for 5.5.x; none yet.

Dylan H.

News Desk

November 25, 2026
2 min read
CISA Warns of Critical Unpatched Danfoss AK-SM 8xxA Flaw (CVE-2026-129713) in Refrigeration Controllers

What happened

CISA has published advisory ICSA-26-328-03 on CVE-2026-129713, a critical flaw in Danfoss AK-SM 8xxA Series controllers (also called the AK-SM 800A Series, including the 820A, 850A and 880A). Food retailers use these devices to manage commercial refrigeration and, depending on the model, lighting and HVAC. BleepingComputer reported the advisory on November 25, 2026.

The vulnerability

ItemDetail
CVECVE-2026-129713
CVSS9.8 (critical)
TypeStack-based buffer overflow in the controller's server
AuthenticationNone needed, per CISA
ImpactServer restart, and potentially remote code execution with web server privileges
FixPlanned for software version 5.5.x; no patch available yet
Vendor advisoryDSA-2026-12-01, published November 20

The reported article does not list affected firmware versions. Danfoss says the 5.5.x update will also remove the option that lets customers disable "Strict mode."

Why it matters

Danfoss AK-SM and AK-SC controllers were already involved in recent attacks on refrigeration systems, according to the same report:

  • October 11 to 12: attacks on French supermarkets and food retailers changed defrost settings on Danfoss and Copeland/Dixell controllers. France attributed them to an IRGC-linked unit.
  • November 2: at least 115 supermarkets in seven European countries had refrigeration shut down or settings changed remotely. Supplier Sabcobel said the same vulnerability from the October attacks was used.
  • November 2: a refrigeration supplier for the French national blood service had cold-storage settings altered at three facilities, with attackers suspected to be part of the same campaign.

The report does not say that CVE-2026-129713 itself has been exploited, and it describes those earlier attacks as using a different, earlier flaw. Treat this one as high risk anyway: it is unauthenticated and there is no patch.

What to do

  • Keep the controllers off the public internet and minimise network exposure.
  • Segregate control systems from business networks and put them behind firewalls.
  • Where remote access is required, use an up-to-date VPN.
  • Check whether any AK-SM 8xxA web interfaces are reachable from outside, and review logs for unexpected restarts.
  • Watch for the 5.5.x release and plan to apply it quickly.

Sources