SECURITYHIGHCVE-2025-41450

CVE-2025-41450: Danfoss AK-SM 800A Improper Authentication Added to CISA KEV (CVSS 8.2)

CISA added CVE-2025-41450 to KEV on Nov 25. A hidden date-based check lets an attacker bypass login on AK-SM 8xxA before 4.2. Update to 4.2 or later.

Dylan H.

Security Team

November 26, 2026
2 min read
CVE-2025-41450: Danfoss AK-SM 800A Improper Authentication Added to CISA KEV (CVSS 8.2)

Actively exploited

Reported as exploited in the wild (e.g. CISA KEV). Patch or mitigate immediately.

Affected Products

  • Danfoss AK-SM 8xxA Series (AK-SM 800A) before software version 4.2

Summary

CVE-2025-41450 is an improper authentication flaw in the Danfoss AK-SM 800A series, a system manager used to monitor and control commercial refrigeration. CISA added it to the Known Exploited Vulnerabilities (KEV) catalog on November 25, 2026. Public reporting rates it CVSS 8.2.

This is a different flaw from the stack buffer overflow covered in CISA Warns of Critical Unpatched Danfoss AK-SM 8xxA Flaw (CVE-2026-129713). Both affect the same product family.

Details

Per public analysis, two undocumented request attributes route the xml.cgi login check to a hidden check_code_of_day function. That function accepts a password derived from the device's date and time, so an attacker who knows the scheme can authenticate without valid credentials.

CISA describes the impact as an attacker being able to generate a web report that exposes sensitive information, including internal IP addresses, usernames and store names.

Exploitation status

  • CISA lists the flaw as exploited, which is the basis for its KEV entry.
  • A public proof-of-concept exists for an unauthenticated remote authentication bypass in the XML interface.
  • Security Affairs reports attacks on internet-exposed refrigeration management interfaces, with default credentials and outdated firmware as likely entry points. It adds that investigators have not confirmed that these specific CVEs were used in those operations.

CISA added two older Danfoss AK-SM 800A flaws, CVE-2023-25914 and CVE-2023-25915, in the same batch.

Fix and deadlines

Danfoss published advisory DSA-2025-03-01 on March 24, 2025, and fixed the flaw in version 4.2. One source says 4.3.1 fixes all three flaws in this KEV batch.

The CISA remediation due date is December 9, 2026 for CVE-2025-41450. For the two 2023 entries it is November 28, 2026.

What to do

  1. Find AK-SM 8xxA units and check their software version. Update to 4.2 or later, ideally the newest release.
  2. Remove the web interface from the internet. Place these controllers behind a VPN or a firewall allow-list.
  3. Change default credentials and review accounts for unknown users.
  4. Check web server logs for unusual requests to xml.cgi and for report generation from unfamiliar addresses.
  5. Treat exposed internal IP addresses, usernames and store names as known to an attacker, and watch for follow-on phishing or access attempts.

Sources